Input Specifications | |
Supply / Monitoring Voltage (Un) Ph - N | : 220 / 230 / 240V* |
Frequency Range | : 48-63 Hz |
Power Consumption | : 15 VA Maximum |
Monitoring Mode | : Under Voltage |
Trip Level (U trip) | : 75% of Un (Factory Set) |
Hysteresis | : 2% (Factory Set) |
Setting Accuracy | : ± 4% |
Delays | |
Power on Delay (t) | : 5 Mins (Min) to 15 Mins (Max) |
From Trip to recovery Time Delay (T2) | : 5 Mins (Min) to 15 Mins (Max) |
(Settable by linear potentiometer) | |
Output | : SPDT Relays |
: AC 15 2A 250V | |
LED Indications | |
Power On | : 3mm Green LED |
Healthy Indication | : 3mm Red LED |
Housing | |
Housing Material | : Polyamide 6.6 |
Colour | : Grey |
Dimension | : 90x56.4x17.5 mm |
Mounting | : TS 35 DIN Rail |
Single Phase Under Voltage Relay
EN1UVR
Features
17.5 mm DIN Rail Mount |
1xSPDT Relay Output |
Green LED for Supply healthy indication |
Red LED for healthy sensing indication |
12 bit sensing |
Product Code | Description | Certification |
EN1UVR | Single Phase Under Voltage Realy 5-15min 1CO | 230 VAC |