Measuring Parameters & Specifications | |
Volts R-N | DirectVoltage Input : 20 to 300V L-N Burden : 0.5VA |
Volts Y-N | |
Volts B-N | |
Volts RY | DirectVoltage Input : Up to 500V L-L Burden : 0.5VA |
Volts YB | |
Volts BR | |
Current R | Secondary Current Input : 5A or 1A (To be specified at the time of Ordering) CT Primary : Site Selectable Range of Reading : 5 – 5000A Burden : < 1.0VA Overload(Through CT) : 5A CT = 6A RMS Continuous 1A CT = 1.2A RMS Continuous (Whole Current) : 120% of Imax continuous. |
Current Y | |
Current B | |
Frequency | 45 to 55 Hz, Accuracy : 0.3% of Reading |
KWh | Range of Reading : 0 to 9999999.9 KWh Accuracy : 1.0S as per IS13779. |
KVARh | Range of Reading: 0 to 9999999.9 KVARh Accuracy : 1.5% of Reading (Between 0.5 Lag to 0.8 Lead |
KVAh | Range of Reading: 0 to 9999999.9 KVAh Accuracy : 1.0% of Reading |
System PF | Accuracy : 1% ofReading (IPFI>0.5) Range of Reading : 0.05 to 1.00 Lag/Lead |
System KVA | Accuracy : 1.0% of Reading |
System KW | Accuracy : 1.0% of Reading |
System KVAR | Accuracy: 1.5% of Reading (Between 0.5 Lag to 0.8 Lead) |
Display | 0.4” Red SevenSegment. |
RS485 | For IntegrationwithEMS/SCADA |
Multifunction Meter with LCD- RS 485 MODBUS
EMF 9620
Features
LCD display with backlight |
Site Programmable CT and PT ratio |
True RMS measurement |
Compact 96 x 96 x 55mm DIN Enclosure |
Micro-controller based |
RS485 computer interface |
Displays with customized LCD |
Autoranging |
Frequency (Hz), Three Energies (kWH, kVAh, KVARh) |
Product Code | Description | Supply Voltage |
EMF 9620 | Mutifunction Meter EMF-9620 nMASTER with RS485 | 230 VAC |