Multifunction Meter- RS 485 MODBUS

EMF 9615

Features

   Bright 0.43" LED Display
   CT Ratio Site Programmable (Primary & Secondary)
   True RMS measurement
   Compact 96 x 96 x 55mm DIN enclosure
   RS 485 computer interface
   Inbuilt Run Hour Feature
   Autoranging
   Micro-controller based

 



Category:

Datasheet



Measuring Parameters & Specifications
Volts R-N Direct Voltage Input : Up to 300V L-N Burden : 0.5VA
Secondary Voltage Input : 63.5V*
Volts Y-N
Volts B-N
Volts RY Direct VoltageInput : Up to 500VL-L Burden : 0.5VA
Secondary Voltage Input : 110V*
Volts YB
Volts  BR
Current R Secondary Current Input : 5A or 1A ( Site Selectable) CT Primary : Site Selectable
Range of Reading : 0 – 5000A Burden : < 1.0VA
Overload(Through CT) : 5A CT = 6A RMS Continuous 1A CT = 1.2A RMS Continuous
(WholeCurrent): 120% of Imaxcontinuous.
Current Y
Current B
Frequency 45 to 55Hz, Accuracy: 0.3% of Reading
KWh Range of Reading : 0 to 9999999.9 KWh Accuracy : 1.0S as per IS13779.
KVAh Range of Reading : 0 to 9999999.9 KWh Accuracy : 1.0% of Reading
System PF Accuracy : 1% of Reading (IPFI>0.5) Range of Reading : 0.05 to 1.00 Lag/Lead
System KVA Accuracy : 1.0% of Reading
System KW Accuracy : 1.0% of Reading (Between 0.5 Lag to 0.8 Lead)
Display 0.4” RedSevenSegment.
RS485 For IntegrationwithEMS/SCADA
Product Code  Description Supply Voltage
EMF 9615  Mutifunction Meter EMF-9615 nPRO with RS485  230 VAC